+86-572-2698168

联系我们

Zhejiang Xingfu Aerospace Technology Co., Ltd.

电话:+86-572-2698168
邮箱:xingfuhangtian@163.com
地址:No. 1688, Ganshan Road, Huzhou, Zhejiang, China
Containerized Power Station

XF3x350GFF Shelter Power Station

【Military Trade Product】
1.jpg

XF3x350GC-9.5M Shelter Power Station

【CEEIC Supporting Product】
2.jpg

XF4×500GC Shelter Power Station

【CEEIC Supporting Product】
Engine ModelYCTD20T330Remote/Local Control FunctionAvailable, Grid-tie with Utility Power Supported
Generator ModelSMF400DEmergency/Interlock Switching FunctionAvailable
Operating Altitude≤3000mSurge Protection/Low Temperature Starting FunctionAvailable
Operating Ambient Temperature-40℃~55℃Chassis Model and ManufacturerKZ1412-01, Two Semi-trailers
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableVoltage WithstandWithstand 1200V Voltage for 1min Without Breakdown or Flashover
Rated Condition OperationContinuous Full-load Operation for 12 HoursSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Power Supply SystemThree-Phase Four-Wire System, External Utility Power ConnectableTransient Voltage/Frequency Regulation Rate≤-15~20%/±7%
Rated Power/Frequency500 2000kW/50HzVoltage/Frequency Fluctuation Rate≤±0.5%/±0.5%
Rated Voltage400V 230VVoltage/Frequency Stabilization Time≤1.0s/3.0s
Rated Power Factor≥0.8 (lagging)No-Load Voltage Setting Range(95% ~ 100%)UN
Overall Dimensions (mm)≤17105×2438×3515High Water Temperature/Low Fuel LevelProtection or Alarm Available
Overall Weight (kg)≤40000 Towing ≤30000Phase Sequence/Overload/Overcurrent/OverloadProtection or Alarm Available
Reliability MTBF2209 hoursOver(Under) Voltage/Low Oil PressureProtection or Alarm Available
Noise dB(A)≤90 (1m distance)Over(Low) Speed Frequency/High Oil TemperatureProtection or Alarm Available
Electromagnetic CompatibilityComplies with GJB151B-2013Low Oil Pressure/Reverse PowerProtection or Alarm Available

XF3×350GC-9.5M Shelter Power Station

【CEEIC Supporting Product】
Engine ModelYCT16T210Remote/Local Control FunctionAvailable, Grid-tie with Utility Power Supported
Generator ModelSMF355DEmergency/Interlock Switching FunctionAvailable
Operating Altitude≤3000mSurge Protection/Low Temperature Starting FunctionAvailable
Operating Ambient Temperature-40℃~55℃Chassis Model and ManufacturerBeiben 4038A
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableVoltage WithstandWithstand 1200V Voltage for 1min Without Breakdown or Flashover
Rated Condition OperationContinuous Full-load Operation for 12 HoursSteady-State Voltage/Frequency Regulation Rate≤±3%/±13%
Power Supply SystemThree-Phase Four-Wire SystemTransient Voltage/Frequency Regulation Rate≤-15~20%/±7%
Rated Power/Frequency350kW (Single Unit) 1050kW (Parallel)/50HzVoltage/Frequency Fluctuation Rate≤±0.5%/±0.5%
Rated Voltage/CurrentAC400V/631A Single UnitVoltage/Frequency Stabilization Time≤1.0s/5.0s
Rated Power Factor≥0.8 (lagging)No-Load Voltage Setting Range(95%~100%)UN
Overall Dimensions (mm)≤9500×300×2130High Water Temperature/Low Fuel LevelProtection or Alarm Available
Overall Weight (kg)≤20000kgPhase Sequence/Overload/Overcurrent/OverloadProtection or Alarm Available
Noise dB(A)/Vibration1200 hoursOver(Under) Voltage/Low Oil PressureProtection or Alarm Available
Reliability MTBF≤90 (1m distance)Over(Low) Speed Frequency/High Oil TemperatureProtection or Alarm Available
Electromagnetic CompatibilityComplies with GJB151B-2013Low Oil Pressure/Reverse PowerProtection or Alarm Available

XF2×50GFF Shelter Power Station

【CEEIC Supporting Product】
Engine ModelMCO5.12JD1Overall Dimensions (mm)3175×2240×1200
Generator ModelUC1224F1Overall Weight (kg)10500
Operating Altitude≤4500mGenerator Insulation ClassH / Monitored
Operating Ambient Temperature-41℃~50℃Noise dB(A)/Vibration≤75 (1m distance)/≤0.3mm
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±3%/±1%
Power Supply SystemThree-Phase AC Power FrequencyTransient Voltage/Frequency Regulation Rate≤-15%,20%/±7%
Rated Power/FrequencySingle 50 Parallel 100kW/50HzVoltage/Frequency Fluctuation≤0.5%/0.5%
Rated Voltage/Current400/230V/90 180AVoltage/Frequency Stabilization Time≤1s/3s
Rated Speed1500r/minNo-Load Voltage Setting Range(95%-105%)UN
Fuel Consumption Rate≤225g/kW.hPhase Sequence/Overload/Short CircuitProtective Measures Available
Oil Consumption Rate≤4.5g/kW.hOver/Under Voltage/Low Oil PressureProtective Measures Available
Fuel Tank Capacity (L)170 (Operable for 8 hours)Overspeed Low Frequency/High Oil TemperatureProtective Measures Available
Reliability MTBF≥1000 hoursNear PowerProtective Measures Available

XF2×75GFF-4 Shelter Power Station

【Bidding & Development Category】
Engine Model6BT5.9-G2Overall Dimensions (mm)2500×1300×1600
Generator ModelUC274COverall Weight (kg)4500kg
Operating Altitude≤3000mGenerator Insulation ClassH / Monitored  ≤300Ω
Operating Ambient Temperature-40℃~50℃Noise dB(A)/Vibration≤80 (1m distance)/≤0.5mm
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Power Supply SystemThree-Phase Four-Wire ACTransient Voltage/Frequency Regulation Rate≤-15%,20%/±5%
Rated Power/Frequency75kW (Parallel)/50HzVoltage/Frequency Fluctuation≤0.5%/0.5%
Rated Voltage/Current400/230V/187AVoltage/Frequency Stabilization Time≤1s/3s
Rated Speed1500r/minNo-Load Voltage Setting Range(85%-110%)UN
Fuel Consumption Rate≤231g/kW.hPhase Sequence/Overload/Short CircuitProtective Measures Available
Oil Consumption Rate≤4.5g/kW.hOver/Under Voltage/Low Oil PressureProtective Measures Available
Fuel Tank Capacity (L)/Overspeed Low Frequency/High Oil TemperatureProtective Measures Available
Reliability MTBF≥3000 hoursElectromagnetic CompatibilityComplies with GJB151B-2013

XF2×150GFF Shelter Power Station

【Military Trade Product】
Engine Model6CTAA8.3-G2Overall Dimensions (mm)8058×2438×2190
Generator ModelUC14C1Overall Weight (kg)11000KG
Operating Altitude≤3000mGenerator Insulation ClassH / Monitored  ≤300Ω
Operating Ambient Temperature-40℃~55℃Noise dB(A)/Vibration≤90 (1m distance)/≤0.5mm
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Power Supply SystemThree-Phase Four-Wire AC Power FrequencyTransient Voltage/Frequency Regulation Rate≤-15%,20%/±5%
Rated Power/Frequency150kW (Single) 300KW (Parallel)/50HzVoltage/Frequency Fluctuation≤0.5%/0.5%
Rated Voltage/Current400/230V/540AVoltage/Frequency Stabilization Time≤1s/3s
Rated Speed1500r/minNo-Load Voltage Setting Range(85%~110%)UN
Fuel Consumption Rate≤226g/kW.hPhase Sequence/Overload/Short CircuitProtective Measures Available
Oil Consumption Rate≤4g/kW.hOver/Under Voltage/Low Oil PressureProtective Measures Available
Fuel Tank Capacity (L)Operable for 6 hoursOverspeed Low Frequency/High Oil TemperatureProtective Measures Available
Reliability MTBF≥1000 hoursNear PowerProtective Measures Available

XF2×200GC Shelter Power Station

【Weapon Supporting Product】
Engine ModelQSZ13-G6Overall Dimensions (mm)6058×2438×2438
Generator ModelHC14FOverall Weight (kg)8625kg
Operating Altitude≤4000mGenerator Insulation ClassH / Monitored  ≤300Ω
Operating Ambient Temperature-25℃~60℃Noise dB(A)/Vibration≤93 (1m distance)/≤0.5mm
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Power Supply SystemThree-Phase Four-Wire AC Power FrequencyTransient Voltage/Frequency Regulation Rate≤-15%,20%/±5%
Rated Power/Frequency200kW/50HzVoltage/Frequency Fluctuation≤0.5%/0.5%
Rated Voltage400/230VVoltage/Frequency Stabilization Time≤1s/3s
Rated Current361A (Single) 1083A (Parallel)No-Load Voltage Setting Range(85%~110%)UN
Fuel Consumption Rate≤225g/kW.hPhase Sequence/Overload/Short CircuitProtective Measures Available
Oil Consumption Rate≤4.0g/kW.hOver/Under Voltage/Low Oil PressureProtective Measures Available
Fuel Tank Capacity (L)820 (2h Operation for 3 Parallel Units)Overspeed Low Frequency/High Oil TemperatureProtective Measures Available
Reliability MTBF≥2000 hoursElectromagnetic CompatibilityProtective Measures Available

XF2x350GC Shelter Power Station

【Aerospace Supporting Product】
3.jpg

XF4x200GFF Shelter Power Station

【CEEIC Supporting Product】
4.jpg

XF3×350GFF Shelter Power Station

【Military Trade Product】
Engine ModelQSZ13-G3Fuel Consumption Rate≤2248g/kW.h
Generator ModelHC134EFuel Tank Capacity (L)880L (Continuous Operation for 4h)
Operating Altitude≤3000mHigh Temperature Adaptability/Wide RangeAdaptable to 45℃ Desert in Northwest China
Operating Ambient Temperature-40℃~55℃Insulation Class/Grounding ResistanceClass H / Monitored ≤30Ω
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Rated Condition Operation12 hoursTransient Voltage/Frequency Regulation Rate≤-15%,20%/±7%
Power Supply SystemThree-Phase Four-Wire ACVoltage/Frequency Fluctuation≤0.5%/0.5%
Rated Power/Frequency350kW (Single) 700KW (Parallel)/50HzVoltage/Frequency Stabilization Time≤1s/3s
Rated Voltage/Current400V/230V/1260A (Parallel)No-Load Voltage Setting Range(85%~115%)UN
Rated Speed/Power Factor1500r/min 0.8 (lagging)Phase Sequence/Overload/Short CircuitProtective Measures Available
Overall Weight (kg)≥19500kgOver/Under Voltage/Low Oil PressureProtective Measures Available
Reliability MTBF≥1000 hoursOver (Under) Voltage/Low Oil PressureProtective Measures Available
Noise dB(A)/Vibration≤85 (1m distance)/≤0.5mmUltra-Low Speed FrequencyProtective Measures Available
Electromagnetic CompatibilityComplies with GJB151B-2013Low Oil Pressure/Reverse PowerProtective Measures Available

XF3×350GC Shelter Power Station

【CEEIC Supporting Product】
Engine ModelWP13D440E310Fuel Consumption Rate≤205g/kW.h
Generator ModelHC1534EFuel Tank CapacityTwo 560L Tanks, Operable for 12h
Operating Altitude≤4500mChassis Model and Manufacturer/
Operating Ambient Temperature-40℃~50℃Remote/Local Control FunctionAvailable
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableInsulation Class/Grounding ResistanceH / Monitored ≤30Ω
Continuous Operation Time12 hoursSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Power Supply SystemThree-Phase Four-Wire AC Power FrequencyTransient Voltage/Frequency Regulation Rate≤±15%/±7%
Rated Power/Frequency350kW 1050kW/50HzVoltage/Frequency Fluctuation Rate≤0.5%/0.5%
Rated Voltage/Current400V 230V/630AVoltage/Frequency Stabilization Time≤1s/3s
Rated Speed/Power Factor1500r/min 0.8 (lagging)No-Load Voltage Setting Range(85%~110%)UN
Overall Dimensions (mm)6058×2733×2050Voltage Waveform Total Harmonic Distortion≤3%
Overall Weight≤13000kgPhase Sequence/Short Circuit/Overload/Overcurrent ProtectionProtective Measures Available
Reliability MTBF≥1000 hoursOver(Under) Voltage/Low Oil Pressure ProtectionProtective Measures Available
Noise dB(A)/Vibration≤90 (1m distance)/≤0.5mmOver(Low) Speed Frequency/High Oil Temperature ProtectionProtective Measures Available
Electromagnetic CompatibilityComplies with GJB151B-2013Low Oil Pressure/Reverse Power ProtectionProtective Measures Available

XF3×350GC700-A Shelter Power Station

【Aerospace Supporting Product】
Engine ModelQSZ13-G3Overall Dimensions (mm)9530×3178×2591
Generator ModelHC1534EOverall Weight≤18000kg
Operating Altitude≤3000mGenerator Insulation ClassH / Monitored ≤30Ω
Operating Ambient Temperature-40℃~55℃Noise dB(A)≤85 (1m distance)
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±3%/±1%
Power Supply SystemThree-Phase Four-Wire ACTransient Voltage/Frequency Regulation Rate≤-15%,20%/±7%
Rated Power/Frequency350 1050kW/50HzVoltage/Frequency Fluctuation Rate≤±0.5%/±0.5%
Rated VoltageAC400VVoltage/Frequency Stabilization Time≤1s/5s
Rated Current630A (Single) 1260A (Parallel)No-Load Voltage Setting Range(85% ~ 110%)UN
Fuel Consumption Rate≤248g/kW.hPhase Sequence/Short Circuit/Overload ProtectionProtective Measures Available
Oil Consumption Rate≤4.0g/kW.hOver/Under Voltage/Low Oil Pressure ProtectionProtective Measures Available
Fuel Tank Capacity (L)880 (Operable for 4 hours)Ultra-Low Speed Frequency/High Oil Temperature ProtectionProtective Measures Available
Reliability MTBF≥1000 hoursReverse Power/Low Battery Voltage ProtectionProtective Measures Available

XF4×200GFF Shelter Power Station

【Military Trade Product】
Engine ModelQSZ13-G6Overall Dimensions (mm)6058×2438×2435
Generator ModelHCI4FOverall Weight (kg)≤11500kg
Operating Altitude≤4000mGenerator Insulation ClassH / Monitored ≤30Ω
Operating Ambient Temperature-25℃~60℃Noise dB(A)/Vibration≤93 (1m distance)/≤0.5mm
Dust, Smoke, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Power Supply SystemThree-Phase Four-Wire AC Power FrequencyTransient Voltage/Frequency Regulation Rate≤-15%,20%/±7%
Rated Power/Frequency200 800kW/50HzVoltage/Frequency Fluctuation Rate≤±0.5%/±0.5%
Rated Voltage400 230VVoltage/Frequency Stabilization Time≤1s/3s
Rated Current361A (Single) 1083A (Parallel)No-Load Voltage Setting Range(85%~110%)UN
Fuel Consumption Rate≤225g/kW.hPhase Sequence/Overload/Short Circuit ProtectionProtective Measures Available
Oil Consumption Rate≤4.0g/kW.hOver/Under Voltage/Low Oil Pressure ProtectionProtective Measures Available
Fuel Tank Capacity (L)820 (2h Operation for 3 Parallel Units)Ultra-Low Speed Frequency/High Oil Temperature ProtectionProtective Measures Available
Reliability MTBF≥1000 hoursReverse Power ProtectionProtective Measures Available

XF4×1000KW Shelter Power Station

【CEEIC Supporting Product】
Engine ModelCummins KTA50-G8Remote/Local/Emergency/Lightning Protection FunctionAvailable
Generator ModelStanford PI734CEngine Room Noise Reduction/Utility Power ATS Switching FunctionAvailable
Operating Altitude≤3000mLight Load Paralleling/Overload Parallel Operation FunctionAvailable
Operating Ambient Temperature-40℃~55℃Fuel Tank Capacity2200L, Continuous Full-Load Operation ≤8 hours
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableVoltage Withstand and Insulation Resistance>2MΩ, Withstand 1440V for 1min Without Breakdown or Flashover
Continuous Operation Time24 Hours of Continuous Operation at Rated ConditionSteady-State Voltage/Frequency Regulation Rate≤±2.5%/±3%
Power Supply SystemThree-Phase Four-Wire System, Neutral Insulation SystemTransient Voltage/Frequency Regulation Rate≤±20%/±7%
Rated Power/Frequency1000kW (Single) 3000kW (Parallel)/50HzVoltage/Frequency Fluctuation Rate≤0.5%/0.5%
Rated Voltage/Current400V/230V, 1800A per Single UnitVoltage/Frequency Stabilization Time≤1s/5s
Rated Speed/Power Factor≥0.8 (lagging)No-Load Voltage Setting Range±(85%~115%)UN
Engine Room Design Dimensions (mm)42000×22000×8000Low Fuel Level, Startup Failure, Rainproof ProtectionProtective Measures Available
Overall Weight (kg)100000Phase Sequence, Short Circuit, Overload, Overcurrent ProtectionProtective Measures Available
Reliability MTBF≥1000 hoursOver(Under) Voltage, Low Oil Pressure, High Water Temperature ProtectionProtective Measures Available
Noise dB(A)/Vibration≤105 (1m distance)/≥0.5mmOver(Low) Speed Frequency, High Oil Temperature, Lightning ProtectionProtective Measures Available
Electromagnetic CompatibilityComplies with GJB151A-97Low Oil Pressure, Reverse Power, Short Circuit ProtectionProtective Measures Available

XF3×1200GC Shelter Power Station

【Aerospace Supporting Product】
Engine Model16M33D1680E310Overall Dimensions (mm)8200×2438×2438
Generator ModelStanford PI734GOverall Weight≤20000kg
Operating Altitude≤3000mGenerator Voltage Withstand LevelMinimum 1200V Withstand Voltage
Operating Ambient Temperature-40℃~55℃Noise dB(A)/Vibration≤90 (1m distance)/≤0.5mm
Dust, Salt Spray, Mold ProtectionProtective Measures AvailableSteady-State Voltage/Frequency Regulation Rate≤±1%/±1%
Power Supply SystemThree-Phase Four-Wire ACTransient Voltage/Frequency Regulation Rate≤-15%,20%/±7%
Rated Power/Frequency3600kW/50HzVoltage/Frequency Fluctuation Rate≤±0.5%/±0.5%
Rated Voltage400V/230VVoltage/Frequency Stabilization Time≤1s/3s
Rated Current/No-Load Voltage Setting Range(85%~110%)UN
Fuel Consumption Rate≤230g/kW.hPhase Sequence/Short Circuit/Overload ProtectionProtective Measures Available
Oil Consumption Rate≤4.0g/kW.hOver/Under Voltage/Low Oil Pressure ProtectionProtective Measures Available
Fuel Tank Capacity (L)Continuous Operation for 4 hoursUltra-Low Speed Frequency/High Oil Temperature ProtectionProtective Measures Available
Reliability MTBF≥1000 hoursReverse Power/Low Battery Voltage ProtectionProtective Measures Available

有什么问题吗?

请随时与我们联系。